14.23
IED status for IEC 60870-5-103 I103IED
14.23.1
Functionality
I103IED is a function block with defined IED functions in monitor direction. This block
uses parameter as
FunctionType
, and information number parameter is defined for each
input signal.
14.23.2
Function block
I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-2-en.vsd
IEC10000292 V2 EN
Figure 281:
I103IED function block
14.23.3
Signals
Table 443:
I103IED Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
19_LEDRS
BOOLEAN
0
Information number 19, reset LEDs
21_TESTM
BOOLEAN
0
Information number 21, test mode is active
22_SETCH
BOOLEAN
0
Information number 22, setting changed
23_GRP1
BOOLEAN
0
Information number 23, setting group 1 is active
24_GRP2
BOOLEAN
0
Information number 24, setting group 2 is active
25_GRP3
BOOLEAN
0
Information number 25, setting group 3 is active
26_GRP4
BOOLEAN
0
Information number 26, setting group 4 is active
14.23.4
Settings
Table 444:
I103IED Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
1MRK 502 048-UUS A
Section 14
Monitoring
625
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...