input signals to the function. In addition, the function generates alarms based on received
information.
14.15.3
Function block
ANSI09000129-1-en.vsd
SSIMG (63)
BLOCK
BLK_ALM
PRESSURE
TEMP
PRES_ALM
PRES_LO
SET_P_LO
SET_T_LO
RESET_LO
PRESSURE
PRES_ALM
PRES_LO
TEMP
TEMP_ALM
TEMP_LO
ANSI09000129 V1 EN
Figure 262:
SSIMG (63) function block
14.15.4
Signals
Inputs PRESSURE and TEMP together with settings
PressAlmLimit
,
PressLOLimit
,
TempAlarmLimit
and
TempLOLimit
are not supported in
this release of 650 series.
Table 420:
SSIMG (63) Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
BLK_ALM
BOOLEAN
0
Block all the alarms
PRESSURE
REAL
0.0
Pressure input from CB
TEMP
REAL
0.0
Temperature of the insulation medium from CB
PRES_ALM
BOOLEAN
0
Pressure alarm signal
PRES_LO
BOOLEAN
0
Pressure lockout signal
SET_P_LO
BOOLEAN
0
Set pressure lockout
SET_T_LO
BOOLEAN
0
Set temperature lockout
RESET_LO
BOOLEAN
0
Reset pressure and temperature lockout
1MRK 502 048-UUS A
Section 14
Monitoring
597
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...