![ABB 650 series Скачать руководство пользователя страница 655](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503655.webp)
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the double point values.
The implementation for IEC61850 quality data handling is restricted to a
simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
16.6
GOOSE function block to receive an integer value
GOOSEINTRCV
16.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive an
integer value
GOOSEINTRCV
-
-
16.6.2
Functionality
GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via
GOOSE.
16.6.3
Function block
IEC10000250-1-en.vsd
GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250 V1 EN
Figure 291:
GOOSEINTRCV function block
1MRK 502 048-UUS A
Section 16
Station communication
649
Technical manual