![ABB 650 series Скачать руководство пользователя страница 647](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503647.webp)
16.2.4
Settings
Table 461:
IEC61850-8-1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
PortSelGOOSE
Front
LAN1
-
-
LAN1
Port selection for GOOSE communication
PortSelMMS
Front
LAN1
Front+LAN1
-
-
LAN1
Port selection for MMS communication
16.2.5
Technical data
Table 462:
Communication protocol
Function
Value
Protocol TCP/IP
Ethernet
Communication speed for the IEDs
100 Mbit/s
Protocol
IEC 61850–8–1
Communication speed for the IEDs
100BASE-FX
Protocol
DNP3.0/TCP
Communication speed for the IEDs
100BASE-FX
Protocol, serial
IEC 60870–5–103
Communication speed for the IEDs
9600 or 19200 Bd
Protocol, serial
DNP3.0
Communication speed for the IEDs
300–115200 Bd
16.3
Horizontal communication via GOOSE for interlocking
16.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Horizontal communication via GOOSE
for interlocking
GOOSEINTLKR
CV
-
-
1MRK 502 048-UUS A
Section 16
Station communication
641
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...