![ABB 650 series Скачать руководство пользователя страница 359](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503359.webp)
TSTSC
BLKSC
BLOCK
TSTAUTSY
AUTOSYOK
PHDIFFME
FRDIFFME
VDIFFME
PHDIFFA
VOKSC
VDIFFSC
OR
AND
AND
AND
AND
AND
AND
phaseAngleDifferenceValue
frequencyDifferenceValue
voltageDifferenceValue
1
1
AND
Note! Similar logic for Manual Synchrocheck.
1
FRDIFFA
ANSI08000018-2-en.vsd
OperationSC = Enabled
VDiffSC
FreqDiffA
PhaseDiffA
Bus voltage >80%
of
GblBaseSelBus
Line voltage >80%
of
GblBaseSelLine
PhaseDiff > 60°
100 ms
INADVCLS
AND
AND
PhaseDiff < 5°
0
0-tSCA
0
50 ms
80 ms
0
ANSI08000018 V2 EN
Figure 164:
Simplified logic diagram for the Auto Synchronism function
12.1.7.3
Synchronizing
When the function is set to
OperationSynch
=
Enabled
the measuring will be performed.
The function will compare the values for the bus and line voltage with internally preset
values that are set to be 80% of the set
UBase
selected for
GlbBaseSelBus
and
GlbBaseSelLine
, which is a supervision that the voltages are both live. Also the voltage
difference is checked to be smaller than the internally preset value 0.10, which is a p.u
value of set voltage base values. If both sides are higher than the preset values and the
1MRK 502 048-UUS A
Section 12
Control
353
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...