7.3.4
Signals
Table 62:
LEXPDIS (40) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Current group connection
U3P
GROUP
SIGNAL
-
Voltage group connection
BLOCK
BOOLEAN
0
Block of function
BLKTRZ1
BOOLEAN
0
Block trip of zone Z1
BLKTRZ2
BOOLEAN
0
Block trip of zone Z2
Table 63:
LEXPDIS (40) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
TRZ1
BOOLEAN
Trip signal from impedance zone Z1
TRZ2
BOOLEAN
Trip signal from impedance zone Z2
START
BOOLEAN
Common start signal
STZ1
BOOLEAN
Pickup signal from impedance zone Z1
STZ2
BOOLEAN
Pickup signal from impedance zone Z2
XOHM
REAL
Reactance in Primary Ohms
XPERCENT
REAL
Reactance in percent of Zbase
ROHM
REAL
Resistance in Primary Ohms
RPERCENT
REAL
Resistance in percent of Zbase
7.3.5
Settings
Table 64:
LEXPDIS (40) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
OperationZ1
Disabled
Enabled
-
-
Enabled
Operation Disable/Enable zone Z1
XoffsetZ1
-1000.00 - 1000.00
%
0.01
-10.00
Offset of Z1 circle top point along X axis in % of
Zbase
Z1diameter
0.01 - 3000.00
%
0.01
100.00
Diameter of imedance circle for Z1 in % of
Zbase
tZ1
0.00 - 6000.00
s
0.01
0.01
Trip time delay for Z1
Table continues on next page
Section 7
1MRK 502 048-UUS A
Impedance protection
168
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...