12.2.4.2
Settings
Table 222:
SXSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tStartMove
0.000 - 60.000
s
0.001
3.000
Supervision time for the apparatus to move
after a command
tIntermediate
0.000 - 60.000
s
0.001
15.000
Allowed time for intermediate position
AdaptivePulse
Not adaptive
Adaptive
-
-
Not adaptive
Output resets when a new correct end position
is reached
tOpenPulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for open command
tClosePulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for close command
SwitchType
Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
-
-
Disconnector
1=LoadBreak,2=Disconnector,3=GroundSw,
4=HighSpeedGroundSw
SuppressMidPos
Disabled
Enabled
-
-
Enabled
Mid-position is suppressed during the time
tIntermediate
12.2.5
Bay control QCBAY
12.2.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Bay control
QCBAY
-
-
12.2.5.2
Functionality
The Bay control QCBAY function is used together with Local remote and local remote
control functions to handle the selection of the operator place per bay. QCBAY also
provides blocking functions that can be distributed to different apparatuses within the bay.
12.2.5.3
Function block
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
IEC09000080_1_en.vsd
IEC09000080 V1 EN
Figure 170:
QCBAY function block
1MRK 502 048-UUS A
Section 12
Control
367
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...