The function IEC60870-5-103 serial communication for RS485, RS485103, is used to
configure the communication parameters for the RS485 serial communication interface.
16.9.2
Settings
Table 481:
OPTICAL103 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SlaveAddress
1 - 255
-
1
1
Slave address
BaudRate
9600 Bd
19200 Bd
-
-
9600 Bd
Baudrate on serial line
RevPolarity
Disabled
Enabled
-
-
Enabled
Invert polarity
CycMeasRepTime
1.0 - 1800.0
s
0.1
5.0
Cyclic reporting time of measurments
MasterTimeDomain
UTC
Local
Local with DST
-
-
UTC
Master time domain
TimeSyncMode
IEDTime
LinMastTime
IEDTimeSkew
-
-
IEDTime
Time synchronization mode
EvalTimeAccuracy
Disabled
5ms
10ms
20ms
40ms
-
-
5ms
Evaluate time accuracy for invalid time
EventRepMode
SeqOfEvent
HiPriSpont
-
-
SeqOfEvent
Event reporting mode
Table 482:
RS485103 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SlaveAddress
1 - 255
-
1
1
Slave address
BaudRate
9600 Bd
19200 Bd
-
-
9600 Bd
Baudrate on serial line
CycMeasRepTime
1.0 - 1800.0
s
0.1
5.0
Cyclic reporting time of measurments
MasterTimeDomain
UTC
Local
Local with DST
-
-
UTC
Master time domain
TimeSyncMode
IEDTime
LinMastTime
IEDTimeSkew
-
-
IEDTime
Time synchronization mode
EvalTimeAccuracy
Disabled
5ms
10ms
20ms
40ms
-
-
5ms
Evaluate time accuracy for invalid time
EventRepMode
SeqOfEvent
HiPriSpont
-
-
SeqOfEvent
Event reporting mode
1MRK 502 048-UUS A
Section 16
Station communication
655
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...