Name
Values (Range)
Unit
Step
Default
Description
UnderTrigLe09
0 - 200
%
1
50
Under trigger level for analog channel 9 in % of
signal
OverTrigOp09
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 9 (on)
or not (off)
OverTrigLe09
0 - 5000
%
1
200
Over trigger level for analog channel 9 in % of
signal
NomValue10
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 10
UnderTrigOp10
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 10
(on) or not (off)
UnderTrigLe10
0 - 200
%
1
50
Under trigger level for analog channel 10 in %
of signal
OverTrigOp10
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 10
(on) or not (off)
OverTrigLe10
0 - 5000
%
1
200
Over trigger level for analog channel 10 in % of
signal
14.4.4
Analog input signals A4RADR
14.4.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Analog input signals
A4RADR
-
-
14.4.4.2
Function block
A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40
IEC09000350-1-en.vsd
IEC09000350 V1 EN
Figure 252:
A4RADR function block, derived analog inputs
Channels 31-40 are not shown in LHMI. They are used for internally
calculated analog signals.
Section 14
1MRK 502 048-UUS A
Monitoring
556
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...