![background image](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503067.webp)
Name
Values (Range)
Unit
Step
Default
Description
OscillationCount10
0 - 255
-
1
0
Oscillation count for input 10
OscillationTime10
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 10
Threshold11
6 - 900
%VB
1
65
Threshold in percentage of station battery
voltage for input 11
DebounceTime11
0.000 - 0.100
s
0.001
0.005
Debounce time for input 11
OscillationCount11
0 - 255
-
1
0
Oscillation count for input 11
OscillationTime11
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 11
Threshold12
6 - 900
%VB
1
65
Threshold in percentage of station battery
voltage for input 12
DebounceTime12
0.000 - 0.100
s
0.001
0.005
Debounce time for input 12
OscillationCount12
0 - 255
-
1
0
Oscillation count for input 12
OscillationTime12
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 12