Table 298:
TMAGGIO Output signals
Name
Type
Description
OUTPUT1
BOOLEAN
OR function betweeen inputs 1 to 16
OUTPUT2
BOOLEAN
OR function between inputs 17 to 32
OUTPUT3
BOOLEAN
OR function between inputs 1 to 32
13.2.5
Settings
Table 299:
TMAGGIO Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Operation Disable / Enable
PulseTime
0.050 - 60.000
s
0.001
0.150
Output pulse time
OnDelay
0.000 - 60.000
s
0.001
0.000
Output on delay time
OffDelay
0.000 - 60.000
s
0.001
0.000
Output off delay time
ModeOutput1
Steady
Pulsed
-
-
Steady
Mode for output 1, steady or pulsed
ModeOutput2
Steady
Pulsed
-
-
Steady
Mode for output 2, steady or pulsed
ModeOutput3
Steady
Pulsed
-
-
Steady
Mode for output 3, steady or pulsed
13.2.6
Operation principle
The trip matrix logic (TMAGGIO) block is provided with 32 input signals and 3 output
signals. The function block incorporates internal logic OR gates in order to provide
grouping of connected input signals to the three output signals from the function block.
Internal built-in OR logic is made in accordance with the following three rules:
1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value 1 the
first output signal (OUTPUT1) will get logical value 1.
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical value
1 the second output signal (OUTPUT2) will get logical value 1.
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1 the
third output signal (OUTPUT3) will get logical value 1.
By use of the settings
ModeOutput1
,
ModeOutput2
,
ModeOutput3
,
PulseTime
,
OnDelay
and
OffDelay
the behavior of each output can be customized. The
OnDelay
is always
active and will delay the input to output transition by the set time. The
ModeOutput
for
respective output decides whether the output shall be steady with an drop-off delay as set
Section 13
1MRK 502 048-UUS A
Logic
472
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...