Figure 64:
Simplified block diagram for ZMRPSB (68) function
7.1.6.5
Operating and inhibit conditions
presents a simplified logic diagram for the Power swing detection function
ZMRPSB (68).
The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh
=
Disabled
, but notice that the
D
Fw and
D
Rv will still be calculated from
RLdOutFw
and
RLdOutRv
. The characteristic will in this case be only quadrilateral.
There are three different ways to form the internal INHIBIT signal:
•
Logical 1 on functional input BLOCK inhibits the output PICKUP signal
instantaneously.
•
The INHIBIT internal signal is activated, if the power swing has been detected and
the measured impedance remains within its operate characteristic for the time, which
Section 7
1MRK 502 048-UUS A
Impedance protection
158
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...