Name
Values (Range)
Unit
Step
Default
Description
Characterist4
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
-
-
ANSI Def. Time
Time delay curve type for step 4
IN4>
1 - 2500
%IB
1
17
Operate residual current level for step 4 in % of
IBase
t4
0.000 - 60.000
s
0.001
1.200
Independent (definite) time delay of step 4
k4
0.05 - 999.00
-
0.01
0.05
Time multiplier for the dependent time delay for
step 4
IMin4
1 - 10000
%IB
1
17
Minimum operate current for step 4 in % of
IBase
t4Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time in inverse curves step 4
HarmRestrain4
Off
On
-
-
On
Enable block of step 4 from harmonic restrain
Table 93:
EF4PTOC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
SeqTypeUPol
ZeroSeq
NegSeq
-
-
ZeroSeq
Choice of measurand for polarizing voltage
SeqTypeIPol
ZeroSeq
NegSeq
-
-
ZeroSeq
Choice of measurand for polarizing current
SeqTypeIDir
ZeroSeq
NegSeq
-
-
ZeroSeq
Choice of measurand for directional current
Section 8
1MRK 502 048-UUS A
Current protection
208
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...