![ABB 650 series Скачать руководство пользователя страница 56](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503056.webp)
Name
Values (Range)
Unit
Step
Default
Description
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim6
1 - 99999
A
1
1000
Rated CT primary current
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
Table 3:
TRM_8I_2U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
Table continues on next page
Section 3
1MRK 502 048-UUS A
Analog inputs
50
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...