Time Integration
Transgression Supervision
Plus Retain
BLOCK
ACCTIME
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC12000195-2-en.vsd
Loop Delay
Loop Delay
tWarning
tOverflow
IEC12000195 V2 EN
Figure 234:
TEIGGIO Simplified logic
TEIGGIO main functionalities are
•
integrate the elapsed time when IN has been high
•
applicable to long time integration (≤999 999.9 seconds)
•
output ACCTIME presents integrated value in seconds to all tools
•
integrated value is retained in non-volatile memory, if any warning, alarm or
overflow occurs
•
any retained value with a warning/alarm/overflow shall be available as the
initiation value for the integration followed by a restart.
•
RESET: Reset the integration value. Consequently all other outputs are also reset
•
unconditionally on the input IN value
•
reset the value of the non-volatile memory to zero.
•
BLOCK: Freeze the integration and block/reset the other outputs
•
unconditionally on the signal value
•
BLOCK request overrides RESET request.
•
Monitor and report the conditions of limit transgression
•
overflow if output ACCTIME >
tOverflow
•
alarm if ACCTIME >
tAlarm
•
warning if ACCTIME >
tWarning
.
The ACCTIME output represents the integrated time in seconds while
tOverflow
,
tAlarm
and
tWarning
are the time limit parameters in seconds.
Section 13
1MRK 502 048-UUS A
Logic
504
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...