![ABB 650 series Скачать руководство пользователя страница 339](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503339.webp)
11.1.5
Settings
Table 200:
SDDRFUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Disable/Enable Operation
OpModeSel
Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
-
-
V0I0
Operating mode selection
3V0PU
1 - 100
%VB
1
30
Pickup of residual overvoltage element in % of
VBase
3I0PU
1 - 100
%IB
1
10
Pickup of residual undercurrent element in % of
IBase
3V2PU
1 - 100
%VB
1
30
Pickup of negative sequence overvoltage
element in % of VBase
3I2PU
1 - 100
%IB
1
10
Pickup of negative sequence undercurrent
element in % of IBase
OpDVDI
Disabled
Enabled
-
-
Disabled
Operation of change based function Disable/
Enable
DVPU
1 - 100
%VB
1
60
Pickup of change in phase voltage in % of
VBase
DIPU
1 - 100
%IB
1
15
Pickup of change in phase current in % of
IBase
VPPU
1 - 100
%VB
1
70
Pickup of phase voltage in % of VBase
50P
1 - 100
%IB
1
10
Pickup of phase current in % of IBase
SealIn
Disabled
Enabled
-
-
Enabled
Seal in functionality Disable/Enable
VSealInPU
1 - 100
%VB
1
70
Pickup of seal-in phase voltage in % of VBase
IDLDPU
1 - 100
%IB
1
5
Pickup for phase current detection in % of
IBase for dead line detection
VDLDPU
1 - 100
%VB
1
60
Pickup for phase voltage detection in % of
VBase for dead line detection
Table 201:
SDDRFUF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
1MRK 502 048-UUS A
Section 11
Secondary system supervision
333
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...