12.12.3
Signals
Table 287:
I103GENCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
Table 288:
I103GENCMD Output signals
Name
Type
Description
CMD_OFF
BOOLEAN
Command output OFF
CMD_ON
BOOLEAN
Command output ON
12.12.4
Settings
Table 289:
I103GENCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
PulseLength
0.000 - 60.000
s
0.001
0.400
Pulse length
InfNo
1 - 255
-
1
1
Information number for command output
(1-255)
12.13
IED commands with position and select for IEC
60870-5-103 I103POSCMD
12.13.1
Functionality
I103POSCMD has double-point position indicators that are getting the position value as
an integer (for example from the POSITION output of the SCSWI function block) and
sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). .The standard does not define
the use of values 0 and 3 . However, when connected to a switching device, these values
are transmitted.
The BLOCK input will block only the signals in monitoring direction (the position
information), not the commands via IEC 60870-5-103. The SELECT input is used to
indicate that the monitored apparatus has been selected (in a select-before-operate type of
control)
1MRK 502 048-UUS A
Section 12
Control
465
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...