Name
Values (Range)
Unit
Step
Default
Description
FunType9
0 - 255
-
1
0
Function type for analog channel 9
(IEC-60870-5-103)
InfNo9
0 - 255
-
1
0
Information number for analog channel 9
(IEC-60870-5-103)
FunType10
0 - 255
-
1
0
Function type for analog channel 10
(IEC-60870-5-103)
InfNo10
0 - 255
-
1
0
Information number for analog channel10
(IEC-60870-5-103)
Table 391:
A1RADR Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
NomValue01
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 1
UnderTrigOp01
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 1
(on) or not (off)
UnderTrigLe01
0 - 200
%
1
50
Under trigger level for analog channel 1 in % of
signal
OverTrigOp01
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 1 (on)
or not (off)
OverTrigLe01
0 - 5000
%
1
200
Over trigger level for analog channel 1 in % of
signal
NomValue02
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 2
UnderTrigOp02
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 2
(on) or not (off)
UnderTrigLe02
0 - 200
%
1
50
Under trigger level for analog channel 2 in % of
signal
OverTrigOp02
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 2 (on)
or not (off)
OverTrigLe02
0 - 5000
%
1
200
Over trigger level for analog channel 2 in % of
signal
NomValue03
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 3
UnderTrigOp03
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 3
(on) or not (off)
UnderTrigLe03
0 - 200
%
1
50
Under trigger level for analog channel 3 in % of
signal
OverTrigOp03
Disabled
Enabled
-
-
Disabled
Use over level trigger for analog channel 3 (on)
or not (off)
OverTrigLe03
0 - 5000
%
1
200
Overtrigger level for analog channel 3 in % of
signal
NomValue04
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 4
UnderTrigOp04
Disabled
Enabled
-
-
Disabled
Use under level trigger for analog channel 4
(on) or not (off)
UnderTrigLe04
0 - 200
%
1
50
Under trigger level for analog channel 4 in % of
signal
Table continues on next page
Section 14
1MRK 502 048-UUS A
Monitoring
554
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...