![ABB 650 series Скачать руководство пользователя страница 128](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503128.webp)
I
N
ROA (Relay Operate Angle)
ROA = 60 deg
REFPDIF never operates for any faults
external to the protected zone.
Currents 3I
o
and I
N
are theoretically
180
o
out of phase for any external
ground-fault.
ANSI05000724 V3 EN
Figure 44:
Zero sequence currents at an external ground fault
Uzs
Uzs
I
N
ANSI05000725 V3 EN
Figure 45:
Zero sequence currents at an internal ground fault
Section 6
1MRK 502 048-UUS A
Differential protection
122
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...