![ABB 650 series Скачать руководство пользователя страница 175](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503175.webp)
Name
Values (Range)
Unit
Step
Default
Description
OperationZ2
Disabled
Enabled
-
-
Enabled
Operation Disable/Enable zone Z2
XoffsetZ2
-1000.00 - 1000.00
%
0.01
-10.00
Offset of Z2 circle top point along X axis in % of
Zbase
Z2diameter
0.01 - 3000.00
%
0.01
200.00
Diameter of imedance circle for Z2 in % of
Zbase
tZ2
0.00 - 6000.00
s
0.01
1.00
Trip time delay for Z2
Table 65:
LEXPDIS (40) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
DirSuperv
Disabled
Enabled
-
-
Disabled
Operation Off/On for additional directional
criterion
XoffsetDirLine
-1000.00 - 3000.00
%
0.01
0.00
Offset of directional line along X axis in % of
Zbase
DirAngle
-180.0 - 180.0
Deg
0.1
-13.0
Angle between directional line and R-axis in
degrees
Table 66:
LEXPDIS (40) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Table 67:
LEXPDIS (40) Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
InvertCTCurr
No
Yes
-
-
No
Invert current direction
7.3.6
Monitored data
Table 68:
LEXPDIS (40) Monitored data
Name
Type
Values (Range)
Unit
Description
XOHM
REAL
-
Ohm
Reactance in Primary Ohms
XPERCENT
REAL
-
%
Reactance in percent of Zbase
ROHM
REAL
-
Ohm
Resistance in Primary Ohms
RPERCENT
REAL
-
%
Resistance in percent of
Zbase
1MRK 502 048-UUS A
Section 7
Impedance protection
169
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...