11.2.3
Function block
GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 161:
Function block
11.2.4
Signals
Table 204:
TCSSCBR Input signals
Name
Type
Default
Description
TCS_STATE
BOOLEAN
0
Trip circuit fail indication from I/O-card
BLOCK
BOOLEAN
0
Block of function
Table 205:
TCSSCBR Output signals
Name
Type
Description
ALARM
BOOLEAN
Trip circuit fault indication
11.2.5
Settings
Table 206:
TCSSCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Operation Disabled/Enabled
tDelay
0.020 - 300.000
s
0.001
3.000
Operate time delay
11.2.6
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are
Enable
and
Disable
.
The operation of trip circuit supervision can be described by using a module diagram. All
the modules in the diagram are explained in the next sections.
1MRK 502 048-UUS A
Section 11
Secondary system supervision
343
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...