![ABB 650 series Скачать руководство пользователя страница 338](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503338.webp)
11.1.3
Function block
ANSI08000220-1-en.vsd
SDDRFUF
I3P*
V3P*
BLOCK
52A
MCBOP
89B
BLKZ
BLKV
3PH
DLD1PH
DLD3PH
ANSI08000220 V1 EN
Figure 156:
SDDRFUF function block
11.1.4
Signals
Table 198:
SDDRFUF Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
52a
BOOLEAN
0
Active when circuit breaker is closed
MCBOP
BOOLEAN
0
Active when external Miniature Circuit Breaker opens
protected voltage circuit
89b
BOOLEAN
0
Active when line disconnect switch is open
Table 199:
SDDRFUF Output signals
Name
Type
Description
BLKZ
BOOLEAN
Start of current and voltage controlled function
BLKV
BOOLEAN
General pickup
3PH
BOOLEAN
Three-phase pickup
DLD1PH
BOOLEAN
Dead line condition in at least one phase
DLD3PH
BOOLEAN
Dead line condition in all three phases
Section 11
1MRK 502 048-UUS A
Secondary system supervision
332
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...