![ABB 650 series Скачать руководство пользователя страница 473](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503473.webp)
Section 13
Logic
13.1
Tripping logic common 3-phase output SMPPTRC (94)
13.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tripping logic common 3-phase output
SMPPTRC
I->O
SYMBOL-K V1 EN
94
13.1.2
Functionality
A function block for protection tripping is provided for each circuit breaker involved in
the tripping of the fault. It provides a settable pulse prolongation to ensure a three-phase
trip pulse of sufficient length, as well as all functionality necessary for correct co-
operation with autoreclosing functions.
The trip function block also includes a settable latch functionality for breaker lock-out.
13.1.3
Function block
ANSI09000284-1-en.vsd
SMPPTRC (94)
BLOCK
TRINP_3P
SETLKOUT
RSTLKOUT
TRIP
CLLKOUT
ANSI09000284 V1 EN
Figure 213:
SMPPTRC (94) function block
1MRK 502 048-UUS A
Section 13
Logic
467
Technical manual