8.7.2.3
Signals
Table 121:
GOPPDOP (32) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLK1
BOOLEAN
0
Block of step 1
BLK2
BOOLEAN
0
Block of step 2
Table 122:
GOPPDOP (32) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
TRIP1
BOOLEAN
Trip signal from stage 1
TRIP2
BOOLEAN
Trip signal from stage 2
BFI_3P
BOOLEAN
General pickup signal
PICKUP1
BOOLEAN
Pickup signal from stage 1
PICKUP2
BOOLEAN
Pickup signal from stage 2
P
REAL
Active Power
PPERCENT
REAL
Active power in % of calculated power base value
Q
REAL
Reactive power
QPERCENT
REAL
Reactive power in % of calculated power base value
8.7.2.4
Settings
Table 123:
GOPPDOP (32) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disable / Enable
OpMode1
Disabled
OverPower
-
-
OverPower
Operation mode 1
Power1
0.0 - 500.0
%
0.1
1.0
Power setting for stage 1 in % of calculated
power base value
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 1
TripDelay1
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 1
OpMode2
Disabled
OverPower
-
-
OverPower
Operation mode 2
Table continues on next page
Section 8
1MRK 502 048-UUS A
Current protection
254
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...