Name
Values (Range)
Unit
Step
Default
Description
k1
0.05 - 999.00
-
0.01
0.05
Time multiplier for the dependent time delay for
step 1
IMin1
1 - 10000
%IB
1
100
Minimum operate current for step1 in % of
IBase
t1Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse curves for
step 1
HarmRestrain1
Off
On
-
-
On
Enable block of step 1 from harmonic restrain
DirMode2
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 2 (off, non-directional,
forward, reverse)
IN2>
1 - 2500
%IB
1
50
Operate residual current level for step 2 in % of
IBase
t2
0.000 - 60.000
s
0.001
0.400
Independent (definite) time delay of step 2
IMin2
1 - 10000
%IB
1
50
Minimum operate current for step 2 in % of
IBase
HarmRestrain2
Off
On
-
-
On
Enable block of step 2 from harmonic restrain
DirMode3
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 3 (off, non-directional,
forward, reverse)
IN3>
1 - 2500
%IB
1
33
Operate residual current level for step 3 in % of
IBase
t3
0.000 - 60.000
s
0.001
0.800
Independent (definite) time delay of step 3
IMin3
1 - 10000
%IB
1
33
Minimum operate current for step 3 in % of
IBase
HarmRestrain3
Off
On
-
-
On
Enable block of step 3 from harmonic restrain
DirMode4
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 4 (off, non-directional,
forward, reverse)
Table continues on next page
1MRK 502 048-UUS A
Section 8
Current protection
207
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...