10.1.7.2
Time delay
The time delay for SAPTUF (81) is a settable definite time delay, specified by the setting
tDelay
.
Trip signal issuing requires that the under frequency condition continues for at least the
user set time delay. If the PICKUP ceases during the delay time, and is not fulfilled again
within a defined reset time, the PICKUP output is reset.
When the measured frequency returns to the level corresponding to the setting
RestoreFreq
, a 100ms pulse is given on the output RESTORE after a settable time delay
(
tRestore
).
10.1.7.3
Blocking
It is possible to block underfrequency protection SAPTUF (81) completely, by binary
input signal:
BLOCK:
blocks all outputs
If the measured voltage level decreases below the setting of
MinValFreqMeas
in the
preprocessing function both the PICKUP and the TRIP outputs are blocked.
10.1.7.4
Design
The design of underfrequency protection SAPTUF (81) is schematically described in
figure
.
Figure 150:
Simplified logic diagram for SAPTUF (81)
10.1.8
Technical data
Table 188:
SAPTUF (81) Technical data
Function
Range or value
Accuracy
Operate value, pickup function
(35.00-75.00) Hz
± 2.0 mHz at
symmetrical three-
phase voltage
Operate value, restore frequency
(45 - 65) Hz
± 2.0 mHz
Reset ratio
<1.001
-
Operate time, pickup function
At 50 Hz: 200 ms typically at f
set
+0.5 Hz to f
set
-0.5 Hz
At 60 Hz: 170 ms typically at f
set
+0.5 Hz to f
set
-0.5 Hz
-
Table continues on next page
Section 10
1MRK 502 048-UUS A
Frequency protection
322
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...