14.1.2.2
Function block
The available function blocks of an IED are depending on the actual hardware (TRM) and
the logic configuration made in PCM600.
CVMMXN
I3P*
V3P*
S
S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
V
V_RANGE
I
I_RANGE
F
F_RANGE
ANSI10000051-1-en.vsd
ANSI10000051 V1 EN
Figure 235:
CVMMXN function block
14.1.2.3
Signals
Table 345:
CVMMXN Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
Table 346:
CVMMXN Output signals
Name
Type
Description
S
REAL
Apparent power magnitude of deadband value
S_RANGE
INTEGER
Apparent power range
P_INST
REAL
Active power
P
REAL
Active power magnitude of deadband value
P_RANGE
INTEGER
Active power range
Q_INST
REAL
Reactive power
Q
REAL
Reactive power magnitude of deadband value
Q_RANGE
INTEGER
Reactive power range
Table continues on next page
1MRK 502 048-UUS A
Section 14
Monitoring
509
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...