parallel connection of current instrument transformers in all three phases
(Holm-Green connection).
•
one single core balance, current instrument transformer (cable CT).
•
one single current instrument transformer located between power system WYE
point and ground (that is, current transformer located in the neutral grounding
of a WYE connected transformer winding).
•
one single current instrument transformer located between two parts of a
protected object (that is, current transformer located between two WYE points
of double WYE shunt capacitor bank).
2. calculated from three-phase current input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC (51N/67N) function
Analog Input I3P is not connected to a dedicated CT input of the IED in PCM600).
In such case the pre-processing block will calculate 3I
0
from the first three inputs into
the pre-processing block by using the following formula (will take I2 from same
SMAI AI3P connected to I3PDIR input (same SMAI AI3P connected to I3P input)):
If zero sequence current is selected,
op
I
3 Io
IA IB IC
= ×
=
+
+
EQUATION2011-ANSI V1 EN
(Equation 47)
where:
IA, IB, IC
are fundamental frequency phasors of three individual phase currents.
The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of the
fundamental frequency component of the residual current is derived. The phasor
magnitude is used within the EF4PTOC (51N/67N) protection to compare it with the set
operation current value of the four steps (
Pickup1
,
Pickup2
,
Pickup3
or
Pickup4
). If the
residual current is larger than the set operation current and the step is used in non-
directional mode a signal from the comparator for this step is set to true. This signal will,
without delay, activate the output signal PU_STx (x=step 1-4) for this step and a common
PICKUP signal.
8.2.7.2
Internal polarizing
A polarizing quantity is used within the protection in order to determine the direction to
the ground fault (Forward/Reverse).
The function can be set to use voltage polarizing, current polarizing or dual polarizing.
Section 8
1MRK 502 048-UUS A
Current protection
210
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...