![ABB 650 series Скачать руководство пользователя страница 283](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503283.webp)
the decrease in the magnitude of the measured voltage quantity. Two different types of
dependencies are available:
•
Voltage restraint overcurrent (when setting parameter
VDepMode
=
Slope
)
VBase
Current Pickup Level
PickupCurr
VDepFact * PickupCurr
VHighLimit
0,25
ANSI10000123-1-en.vsd
ANSI10000123 V1 EN
Figure 126:
Example for current pickup level variation as function of measured
voltage magnitude in Slope mode of operation
•
Voltage controlled overcurrent (when setting parameter
VDepMode
=
Step
)
1MRK 502 048-UUS A
Section 8
Current protection
277
Technical manual