Name
Values (Range)
Unit
Step
Default
Description
IMagComp5
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 5% of In
IMagComp30
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 30% of
In
IMagComp100
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at 100%
of In
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 5% of In
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 30% of In
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 100% of In
14.1.3.5
Monitored data
Table 354:
CMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
I_A
REAL
-
A
IA Amplitude
IA_ANGL
REAL
-
deg
IA Angle
I_B
REAL
-
A
IB Amplitude
IB_ANGL
REAL
-
deg
IB Angle
I_C
REAL
-
A
IC Amplitude
IC_ANGL
REAL
-
deg
IC Angle
14.1.4
Phase-phase voltage measurement VMMXU
14.1.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase-phase voltage measurement
VMMXU
U
SYMBOL-UU V1 EN
-
14.1.4.2
Function block
The available function blocks of an IED are depending on the actual hardware (TRM) and
the logic configuration made in PCM600.
Section 14
1MRK 502 048-UUS A
Monitoring
516
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...