Current I2-1>
Operate
time
t1Min
t1Max
(Default= 1000 s)
(Default= 5 s)
K1
IEC09000691-2-en.vsd
IEC09000691 V2 EN
Figure 122:
Inverse time characteristic with t1Min and t1Max
For a detailed description of inverse time characteristic, see chapter
.
The reset time is exponential and is given by the following expression:
ResetTime s
ResetMultip
I
I
NS
Pickup
[ ]
−
=
⋅
2
1
K
K
1
ANSIEQUATION2111 V1 EN
(Equation 74)
Where
I
NS
is the measured negative sequence current
I
Pickup
is the desired pickup level in pu of rated generator current
ResetMultip
is multiplier of the generator capability constant
K equal to setting K1 and thus defines reset
time of inverse time characteristic
Section 8
1MRK 502 048-UUS A
Current protection
270
Technical manual