Sigma II User’s Manual
Chapter 5: Parameter Settings and Functions
5-77
The following parameter setting is used to change the CN1 connector terminal that
outputs the /TGON signal.
The parameter is default set so the /TGON signal is output between CN1-27 and 28.
See
5.3.4 Output Circuit Signal Allocation
for more details on parameter Pn50E.
This parameter is used to set output conditions for the operation detection output
signal /TGON.
This parameter is used to set the speed at which the servo amplifier determines that
the servomotor is running and then to output an appropriate signal. The following
signals are generated when motor speed exceeds the preset level.
Signals generated when servomotor operation is detected:
•
/TGON
•
Status Indication Mode
•
Monitor Mode Un006
Parameter
Signal
Setting
(rpm)
Description
Pn50E
Output Signal Selections 1
Default Setting: 3211
Position Control
Parameter
Signal
Setting
(rpm)
Description
Pn502
Rotation Detection Level
Setting Range: 1 to 10000
Default Setting: 20
Speed/Torque Control,
Position Control
Motor speed
(Un000)
/TGON
Pn502
Summary of Contents for SGMAH
Page 1: ...Sigma II Series Servo System User s Manual...
Page 2: ......
Page 4: ...ii This page intentionally left blank...
Page 6: ...iv This page intentionally left blank...
Page 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Page 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Page 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Page 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Page 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Page 487: ......