Sigma II User’s Manual
Chapter 7: Using the Digital Operator
7 - 45
Manual Zero Adjustment of Analog Monitor Output
Follow the procedure below to execute the manual zero adjustment of analog
monitor output.
Using the Hand-held Digital Operator
1.
Press the
DSPL/SET
key to select the auxiliary function mode.
2.
Select the parameter Fn00C.
Press the
Left Arrow
or
Right Arrow
key to select the digit.
Press the
Up Arrow
or
Down Arrow
key to change the value.
3.
Press the
DATA/ENTER
key, and the display will be as shown below.
4.
Press the
DSPL/SET
key. Each time the
MODE/SET
key is pressed, the
monitor output will toggle between the displays for the two channels shown
below.
5.
Press the
Left Arrow
or
Right Arrow
key to display the analog monitor
output data. Pressing the
Left Arrow
or
Right Arrow
key again will
return to the display shown in the above step 3 or 4.
6.
Press the
Up Arrow
or
Down Arrow
key to perform zero adjustment of the
analog monitor output.
7.
When zero adjustment has been completed for the two channels, press the
DATA/ENTER
key to return to the auxiliary function mode display.
DSPL/SET Key
Displayed
alternately
Data Display
Displayed
alternately
LEFT Cursor Key
(RIGHT Cursor Key) Data Display
Data Setting Change
Summary of Contents for SGMAH
Page 1: ...Sigma II Series Servo System User s Manual...
Page 2: ......
Page 4: ...ii This page intentionally left blank...
Page 6: ...iv This page intentionally left blank...
Page 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Page 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Page 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Page 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Page 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Page 487: ......