Sigma II User’s Manual
Chapter 5: Parameter Settings and Functions
5-57
5.3.4
Output Circuit Signal Allocation
Output Signal Allocation
Output signal functions can be allocated to the sequence signal output circuits shown
below.
Output Signal Selection Default Settings
The output signal selection parameters and their default settings are shown below.
Select the CN1 connector terminals that will output the signals.
CN1 Connector
Terminal
Numbers
Output Terminal
Name
Default Setting
Comments
Symbol
Name
25
SO1
/V-CMP+
(/COIN+)
Speed coincidence
detection (positioning
completed)
The signal output
will vary depending
on the control mode.
26 (SG)
/V-CMP–
(/COIN–)
27
SO2
/TGON+
Rotation detection
—
28 (SG)
/TGON–
29
SO3
/S-RDY+
Servo ready
—
30 (SG)
/S-RDY–
Parameter
Signal
Setting
Description
Pn50E
Output Signal Selections 1
Default Setting: 3211
Speed/Torque Control,
Position Control
Pn50F
Output Signal Selections 2
Default Setting: 0000
Speed/Torque Control,
Position Control
Pn510
Output Signal Selections 3
Default Setting: 0000
Speed/Torque Control,
Position Control
Output
signal
1
2
3
SO1 (CN1-25, 26)
SO2 (CN1-27, 28)
SO3 (CN1-29, 30)
Pn50E.
t
o Pn510
.
Summary of Contents for SGMAH
Page 1: ...Sigma II Series Servo System User s Manual...
Page 2: ......
Page 4: ...ii This page intentionally left blank...
Page 6: ...iv This page intentionally left blank...
Page 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Page 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Page 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Page 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Page 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Page 487: ......