This completes the manual zero adjustment of the analog monitor output.
Using the Built-in Panel Operator
1.
Press the
MODE/SET
key to select the auxiliary function mode.
2.
Press the
Up Arrow
or
Down Arrow
key to select the parameter Fn00C.
3.
Press the
DATA/SHIFT
key for a minimum of one second, and the display will
be as shown below.
4.
Press the
MODE/SET
key. Each time the
MODE/SET
key is pressed, the
monitor output will toggle between the displays for the two channels shown
below.
5.
Press the
DATA/SHIFT
key for less than one second, and the analog monitor
gain parameter will be displayed. Pressing the
DATA/SHIFT
key again for less
than one second will return to the display shown in the above steps 3 or 4.
6.
Press the
Up Arrow
or
Down Arrow
key to perform zero adjustment of the
analog monitor output.
7.
When zero adjustment has been completed for the two channels, press the
DATA/SHIFT
key for a minimum of one second to return to the auxiliary
function mode display.
This completes the manual zero adjustment of the analog monitor output.
SGDM-
MODE/SET
DATA/
CHARGE
POWER
SERVOPACK
200V
YASKAWA
MODE/SET Key
Displayed
Alternately
Data Display
DATA/SHIFT Key
Displayed
Alternately
Data Setting Change
Summary of Contents for SGMAH
Page 1: ...Sigma II Series Servo System User s Manual...
Page 2: ......
Page 4: ...ii This page intentionally left blank...
Page 6: ...iv This page intentionally left blank...
Page 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Page 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Page 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Page 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Page 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Page 487: ......