YASKAWA
TOMPYEULA7002A LA700 Series Installation and Operation Instruction
369
Model
Terminal
Recomm. Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
(mm
2
)
IP20 Applicable
Gauge
AWG, kcmil
(mm
2
)
Wire Stripping
Length
mm
Terminal Screw
Size and Shape
Tightening
Torque
N
∙
m (lbf
∙
in)
4270
R/L1, S/L2, T/L3
2/0 × 2P
1 - 2/0 × 2P
(50 - 70 × 2P)
2/0 × 2P
(70 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3
2/0 × 2P
1 - 2/0 × 2P
(50 - 70 × 2P)
2/0 × 2P
(70 × 2P)
-
M10
20
(177)
-, +1
4/0 × 2P
2/0 - 4/0 × 2P
(70 - 95 × 2P)
4/0 × 2P
(95 × 2P)
-
M10
20
(177)
+3
1/0 × 2P
2 - 1/0 × 2P
(35 - 50 × 2P)
1/0 × 2P
(50 × 2P)
-
M10
20
(177)
2
4 - 350
(25 - 150)
-
-
M10
18 - 23
(159 - 204)
4325
R/L1, S/L2, T/L3
2/0 × 2P
1 - 2/0 × 2P
(50 - 70 × 2P)
2/0 × 2P
(70 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3
2/0 × 2P
1 - 2/0 × 2P
(50 - 70 × 2P)
2/0 × 2P
(70 × 2P)
-
M10
20
(177)
-, +1
4/0 × 2P
2/0 - 4/0 × 2P
(70 - 95 × 2P)
4/0 × 2P
(95 × 2P)
-
M10
20
(177)
+3
1/0 × 2P
2 - 1/0 × 2P
(35 - 50 × 2P)
1/0 × 2P
(50 × 2P)
-
M10
20
(177)
2
2 - 350
(35 - 185)
-
-
M10
18 - 23
(159 - 204)
4380
R/L1, S/L2, T/L3
250 × 2P
3/0 - 250 × 2P
(95 - 120 × 2P)
250 × 2P
(120 × 2P)
-
M12
35
(310)
U/T1, V/T2, W/T3
250 × 2P
3/0 - 250 × 2P
(95 - 120 × 2P)
250 × 2P
(120 × 2P)
-
M12
35
(310)
-, +1
300 × 2P
4/0 - 300 × 2P
(95 - 150 × 2P)
300 × 2P
(150 × 2P)
-
M12
35
(310)
+3
300 × 2P
4/0 - 300 × 2P
(95 - 150 × 2P)
300
(150)
-
M12
35
(310)
1
1 - 350
(50 - 185)
-
-
M12
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges. If your installation does not need IP20 protection, smaller
cables can be used.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than 30 mm
2
(AWG 8), tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lbf∙in to 40 lbf∙in).
*4
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.