362
YASKAWA
TOMPYEULA7002A LA700 Series Installation and Operation Instruction
Figure 10.8 Wiring Example for DC Power Supply Input
WARNING
Electrical Shock Hazard. Do not ground the main circuit bus. Incorrect wiring can cause serious injury or
death.
Note:
•
Install a fuse for each drive when operating more than one drive. If one fuse blows, replace all fuses.
•
Install the external filter (system) to comply with the EMC Directive.
Refer to
and
for the recommended fuses.
Table 10.13 Recommended Fuse (Three-Phase 200 V Class)
Drive Model
Fuse
Manufacturer: Bussmann
Model
Qty
2022
FWH-80B
2
2031
FWH-125B
2
2041
FWH-150B
2
2059
FWH-200B
2
2075
FWH-250A
2
2094
FWH-250A
FWH-300A
2
2110
FWH-250A
FWH-275A
2
2144
FWH-300A
FWH-350A
2
Drive Model
Fuse
Manufacturer: Bussmann
Model
Qty
2181
FWH-350A
FWH-450A
2
2225
FWH-450A
FWH-600A
2
2269
FWH-600A
FWH-700A
2
2354
FWH-800A
2
2432
FWH-1000B
2
2519
FWH-1000B
2
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Table 10.14 Recommended Fuse (Three-Phase 400 V Class)
Drive Model
Fuse
Manufacturer: Bussmann
Model
Qty
4012
FWH-60B
2
4019
FWH-80B
2
4023
FWH-90B
2
4030
FWH-150B
2
4039
FWH-200B
2
4049
FWH-200B
2
4056
FWH-225A
2
4075
FWH-250A
2
4094
FWH-275A
2
4114
FWH-275A
2
Drive Model
Fuse
Manufacturer: Bussmann
Model
Qty
4140
FWH-300A
FWH-325A
2
4188
FWH-400A
FWH-450A
2
4225
FWH-500A
FWH-600A
2
4270
FWH-600A
FWH-700A
2
4325
FWH-700A
FWH-800A
2
4380
FWH-800A
2
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.