The control circuit is a Safety Extra-Low Voltage circuit. Separate this circuit from other circuits with reinforced insulation. Make
sure that the Safety Extra-Low Voltage circuit is connected as specified.
*4
Reinforced insulation separates the output terminals from other circuits. Users can also connect circuits that are not Safety Extra-Low
Voltage circuits if the drive output is 250 Vac 1 A maximum or 30 Vdc 1 A maximum.
■
Control Circuit Terminals
Control Circuit Wire Gauges and Tightening Torques
NOTICE
Do not let wire shields touch other signal lines or equipment. Insulate the wire shields with electrical tape or
shrink tubing. If you do not insulate the wire shields, it can cause a short circuit and damage the drive.
Use shielded wire to wire the control circuit terminal block. Use crimp ferrules on the wire ends to make the
wiring procedure easier and more reliable.
Table 1.7 Control Circuit Wire Gauges and Tightening Torques
Terminal Block
Terminal
Screw
Size
Tightening
Torque
N
∙
m (lbf
∙
in)
Bare Wire
Crimp Ferrule
Recomm. Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
Recomm. Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
TB1
S1-S8, SN, SC, SP
-
-
0.75
(18)
•
Stranded wire
0.2 - 1.0
(24 - 18)
•
Solid wire
0.2 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
TB2-1
MA, MB, MC
TB2-2
M1, M2, M5
TB2-3
M3, M4, M6
TB3
+V, AC, -V, A1, A2, A3, FM,
AM, AC, P1, C1, S9
TB4
E (G), SN, HC, H1, H2, PS, AC,
D +, D-, P2, C2, S10
TB5
E (G)
M3.5
0.5 - 1.0
(4.4 - 8.9)
0.5 - 2
(20 - 14)
1.25
(12)
-
-
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
Figure 1.8 External Dimensions of Crimp Ferrules
Table 1.8 Crimp Ferrule Models and Sizes
Wire Gauge
mm
2
(AWG)
Model
L (mm)
L1 (mm)
φ
d1 (mm)
φ
d2 (mm)
0.25 (24)
AI 0.25-8YE
12.5
8
0.8
2.0
0.34 (22)
AI 0.34-8TQ
12.5
8
0.8
2.0
0.5 (20)
AI 0.5-8WH,
AI 0.5-8OG
14
8
1.1
2.5
◆
Drive Start-Up
■
Drive Setup Procedure
shows the basic setup procedure. This section gives more information about the steps to take after you
energize the drive.