366
YASKAWA
TOMPYEULA7002A LA700 Series Installation and Operation Instruction
Model
Terminal
Recomm. Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
(mm
2
)
IP20 Applicable
Gauge
AWG, kcmil
(mm
2
)
Wire Stripping
Length
mm
Terminal Screw
Size and Shape
Tightening
Torque
N
∙
m (lbf
∙
in)
2519
R/L1, S/L2, T/L3
250 × 2P
3/0 - 300 × 2P
(95 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
35
(310)
U/T1, V/T2, W/T3
250 × 2P
3/0 - 300 × 2P
(95 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
35
(310)
-, +1
300 × 2P
4/0 - 300 × 2P
(95 - 150 × 2P)
300 × 2P
(150 × 2P)
-
M12
35
(310)
+3
300 × 2P
4/0 - 300 × 2P
(95 - 150 × 2P)
300
(150)
-
M12
35
(310)
1
1 - 350
(50 - 185)
-
-
M12
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges. If your installation does not need IP20 protection, smaller
cables can be used.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
When you use AWG 8 or larger wires to comply with UL standards, tighten the screws to a tightening torque of 4.1 N∙m to 4.5 N∙m
(36 lbf∙in to 40 lbf∙in).
*4
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*5
A junction terminal is necessary to connect a braking unit (CDBR-series) to terminals - and +3.
Three-Phase 400 V Class
Model
Terminal
Recomm. Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
(mm
2
)
IP20 Applicable
Gauge
AWG, kcmil
(mm
2
)
Wire Stripping
Length
mm
Terminal Screw
Size and Shape
Tightening
Torque
N
∙
m (lbf
∙
in)
4012
R/L1, S/L2, T/L3
14
14 - 12
(2.5 - 4.0)
14 - 12
(2.5 - 4.0)
10
M4
1.5 - 1.7
(13.3 - 15)
U/T1, V/T2, W/T3
14
14
(2.5)
14
(2.5)
10
M4
1.5 - 1.7
(13.3 - 15)
-, +1, +2
12
14 - 12
(2.5 - 4.0)
14 - 12
(2.5 - 4.0)
18
M5
2.3 - 2.5
(20.3 - 22.1)
B1, B2
14
14
(2.5)
14
(2.5)
10
M4
1.5 - 1.7
(13.3 - 15)
10
14 - 10
(2.5 - 6.0)
-
-
M4
1.2 - 1.5
(10.6 - 13.3)
4019
R/L1, S/L2, T/L3
12
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
10
M4
1.5 - 1.7
(13.3 - 15)
U/T1, V/T2, W/T3
12
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
10
M4
1.5 - 1.7
(13.3 - 15)
-, +1, +2
10
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
18
M5
2.3 - 2.5
(20.3 - 22.1)
B1, B2
14
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
10
M4
1.5 - 1.7
(13.3 - 15)
10
14 - 10
(2.5 - 6.0)
-
-
M5
2.0 - 2.5
(17.7 - 22.1)
4023
R/L1, S/L2, T/L3
10
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
10
M4
1.5 - 1.7
(13.3 - 15)
U/T1, V/T2, W/T3
12
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
10
M4
1.5 - 1.7
(13.3 - 15)
-, +1, +2
10
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
18
M5
2.3 - 2.5
(20.3 - 22.1)
B1, B2
14
14 - 10
(2.5 - 6.0)
14 - 10
(2.5 - 6.0)
10
M4
1.5 - 1.7
(13.3 - 15)
10
14 - 10
(2.5 - 6.0)
-
-
M5
2.0 - 2.5
(17.7 - 22.1)