YASKAWA
TOMPYEULA7002A LA700 Series Installation and Operation Instruction
353
Model
Recomm. Gauge (AWG, kcmil)
Terminal
Screw Size
Crimp
Terminal
Model
Crimping Tool
Insulation
Cap Model
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
-, +1
+3
Tool Model
Die Jaw
4325
2/0 × 2P
2/0 × 2P
-
-
-
M10
80-10
YF-1
YET-150-1
TD-227, TD-
214
TP-080
-
-
4/0 × 2P
-
-
M10
R100-10
YF-1
YET-150-1
TD-228, TD-
214
TP-100
-
-
-
1/0 × 2P
-
M10
R60-10
YF-1
YET-150-1
TD-225, TD-
213
TP-060
-
-
-
-
2
M10
R38-10
YF-1
YET-150-1
TD-224, TD-
212
TP-038
4380
250 × 2P
250 × 2P
-
-
-
M12
R150-12
YF-1
YET-300-1
TD-325, TD-
313
TP-150
-
-
300 × 2P
300 × 2P
-
M12
R150-12
YF-1
YET-300-1
TD-325, TD-
313
TP-150
-
-
-
-
1
M12
R60-12
YF-1
YET-300-1
TD-321, TD-
311
TP-060
Factory-Recommended Branch Circuit Protection for UL Listing
Use branch circuit protection to protect against short circuits and to maintain compliance with UL 61800-5-1.
Yaskawa recommends connecting semiconductor protection fuses on the input side for branch circuit protection.
Refer to
and
for more information about recommended fuses.
WARNING
Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not immediately energize the
drive or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all
indicators are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the
cause of the problem, contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before
you operate the drive or peripheral devices, it can cause serious injury or death.
•
200 V Class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS and not more than 240 Vac when there is a short circuit in the power supply.
•
400 V Class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
100,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric Code (NEC), the Canadian Electric Code, Part I
(CEC), and local codes.
Three-Phase 200 V Class
Table 10.4 Factory-Recommended Branch Circuit Protection: 200 V Class
Drive Model
Maximum Applicable Motor Output
kW (HP)
Input Current Rating
A
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
2022
3.7 (5)
18.2
FWH-80B
2031
5.5 (7.5)
26.5
FWH-125B
2041
7.5 (10)
35.5
FWH-150B
2059
11 (15)
51.2
FWH-200B
2075
15 (20)
69
FWH-225A
2094
18.5 (25)
84.4
FWH-225A
2110
22 (30)
72
FWH-225A
2144
30 (40)
97.3
FWH-275A
2181
37 (50)
119.2
FWH-275A
2225
45 (60)
144.3
FWH-325A
2269
55 (75)
175.4
FWH-600A