Settings
99
Index
Sub-ind
ex
Name
Unit
Setting range
Default
value
effective
Period
0x02-
Confirm with 200ms delay;
0x03-
Confirm with 400ms delay;
0x04-
Confirm with 600ms delay;
0x05- Confirm with 1000ms delay.
Byte3: Reserved
Index
Sub-ind
ex
Name
Unit
Setting range
Default
value
effective
Period
0x219A
0
Fault Reaction Stop
Option 5
-
0~0x00070707
0x00000
501
Restart
Y
Set the fault stop options for group 5.
Byte0: Fault reaction stop option code
0x00- Disable drive function, and the motor stops with dynamic brake ON;
0x01- Disable drive function, and the motor stops freely;
0x02-
Slow down on slow down ramp and disable drive function;
0x03- Slow down on quick stop ramp and disable drive function;
0x04-
Stop immediately and disable drive function;
Byte1: Fault reaction priority
0x00-Priority 8;
0x01-Priority 7;
0x02-Priority 6;
0x03-Priority 5;
0x04-Priority 4;
0x05-Priority 3;
0x06-Priority 2;
0x07-Priority 1.
The higher the number, the higher the priority.
Byte2: Fault confirmation delay time option code
0x00-
Confirm immediately without delay;
0x01-
Confirm with 100ms delay;
0x02-
Confirm with 200ms delay;
0x03-
Confirm with 400ms delay;
0x04-
Confirm with 600ms delay;
0x05- Confirm with 1000ms delay.
Byte3: Reserved