Maintenance
261
Number
Alarm name
Alarm
code
Possible causes
Solutions
87.
CPU overheating
0xFF67
1.
The temperature sampling
circuit inside the drive is
abnormal
2.
The temperature of the
drive's
operating
environment is beyond the
allowed range
1.
Reduce
the
ambient
temperature
2.
Restart or replace the drive
88.
CPU1 overload
0xFF68
1.
The drive's operation is
disturbed
2.
The internal circuit of the
drive is abnormal
3.
The debugging software's
functions are over-used
1.
Conduct standard peripheral
wiring for the drive, and
enhance
the
anti-interference measures
2.
Replace the drive
3.
Disable some functions of
the debugging software
89.
CPU2 overload
0xFF69
1.
The drive's operation is
disturbed
2.
The internal circuit of the
drive is abnormal
3.
The debugging software's
functions are over-used
1.
Conduct standard peripheral
wiring for the drive, and
enhance
the
anti-interference measures
2.
Replace the drive
3.
Disable some functions of
the debugging software
90.
CPU1 shakehand failed
0xFF70
There is a problem inside the
drive
Restart or replace the drive
91.
DrivePro
Communication
timeout
0xFF71
1.
The drive's debugging cable
is
disconnected
or
not
reliably connected
2.
The communication of the
drive's debugging serial port
is interrupted
1.
Check the wiring of the
drive's debugging cable and
make
sure
that
the
connection is reliable
2.
Replace the debugging cable
with one with isolated serial
port
3.
Enhance
the
anti-interference measures
of the debugging cable, for
example, by adding magnetic
ring,
conducting
reliable
grounding of the debugging
computer, powering on the
debugging
computer
separately from the drive
Summary of Contents for CoolDrive Series
Page 29: ...Preface 17 T2 model ...
Page 30: ...Preface 18 T3 model ...
Page 31: ...Preface 19 T4 model ...
Page 230: ...Monitoring 218 ...