Page EN-20
SITRANS LR200 (HART) – QUICK START MANUAL
7ML19985XC81
mmmmm
English
1.5. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty level.
1.6. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level.
1.7. Apply? (Apply changes)
In order to save the Quick Start settings it is necessary to select Yes to apply changes.
Display shows DONE when Quick Start is successfully completed.
Press Mode
to return to Measurement mode. SITRANS LR200 is now ready to operate.
Requesting an Echo Profile
1)
In PROGRAM mode, navigate to: Level Meter >
Diagnostics (3) > Echo Profile (3.1).
2)
Press RIGHT arrow
to request a profile.
3)
In the Profile screen, press UP arrow
to select
the Transmit icon, and RIGHT arrow
to update
the profile.
4)
Press DOWN arrow
to select the Exit icon,
then RIGHT arrow
to return to previous menu.
SITRANS LR200 Communications: HART
• You will need the full manual to acquire the list of applicable parameters.
• We recommend that you use SIMATIC Process Device Manager (PDM) to program your
device.
SIMATIC PDM
SIMATIC PDM is a software package used to commission and maintain SITRANS LR200 and
other process devices. Please consult the operating instructions or online help for details on
using SIMATIC PDM. (You can find more information at: www.siemens.com/simatic-pdm. Go to
Products and Solutions > Products and Systems > Communications and Software > Process
Device Manager.)
Values
Range: 0.0000 to 20.000 m
Values
Range: 0.0000 to 20.000 m
Options
YES, NO
Notes:
• SIMATIC PDM Rev. 6.0 SP3 or higher is recommended.
• SIMATIC PDM Rev. 5.2 SP1 is supported only for basic configuration and troubleshooting.
For advanced features such as the Quick Start wizard, Revision 6.0 SP3 or higher is
required.
DIAGNOSTICS
MEAS. VALUES
REMAIN. DEV. LIFE
RE
.
MAIN SENS. LIFE
3.1
ECHO PROFILE
C:38 A:TF D:4.25
1
2
3
4
5
transmit icon,
selected
exit icon,
deselected
transmit icon,
deselected
exit icon,
selected
Summary of Contents for Sitrans LR200
Page 1: ...Quick Start Manual May 2008 LR200 HART sitrans ...
Page 25: ...Page EN 24 SITRANS LR200 HART QUICK START MANUAL 7ML19985XC81 mmmmm English Notes ...
Page 49: ...Side DK 24 SITRANS LR200 HART QUICK START MANUAL 7ML19985XC81 mmmmm Dansk Bemærkninger ...
Page 73: ...Seite DE 24 SITRANS LR200 HART KURZANLEITUNG 7ML19985XC81 mmmmm Deutsch Notizen ...
Page 74: ...7ML19985XC81 SITRANS LR200 HART KURZANLEITUNG Seite DE 25 mmmmm Deutsch ...
Page 75: ...Seite DE 26 SITRANS LR200 HART KURZANLEITUNG 7ML19985XC81 mmmmm Deutsch ...
Page 123: ...Página ES 24 SITRANS LR200 HART ARRANQUE RÁPIDO 7ML19985XC81 mmmmm Español Notas ...
Page 147: ...Page FR 24 SITRANS LR200 HART MISE EN SERVICE RAPIDE 7ML19985XC81 mmmmm Français Remarques ...
Page 171: ...Pagina IT 24 SITRANS LR200 HART AVVIO RAPIDO 7ML19985XC81 mmmmm Italiano Nota ...
Page 196: ...7ML19985XC81 SITRANS LR200 HART QUICK START HANDLEIDING pagina NL 25 mmmmm Nederlands ...
Page 197: ...Pagina NL 26 SITRANS LR200 HART QUICK START HANDLEIDING 7ML19985XC81 mmmmm Nederlands ...
Page 245: ...Sivu SU 24 SITRANS LR200 HART PIKAKÄYTTÖOPAS 7ML19985XC81 mmmmm Suomi Huomautukset ...
Page 269: ...Sida SE 24 SITRANS LR200 HART SNABBSTARTSMANUAL 7ML19985XC81 mmmmm Svenska Anmärkningar ...