9.18
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Event Reports and SER
Standard 15-, 30-, or 60-Cycle Event Reports
Figure 9.7
Derivation of Phasor RMS Current Values From Event Report
Current Values
, note that two rows of current data one-quarter cycle apart can be
used to calculate phasor rms current values. At the time of interest, the present
sample is used as the Real Axis, or “X” component, while the value from one-
quarter cycle before is used as the Imaginary Axis, or “Y” component.
Plotting the components as shown, and noting that the angle of the phasor is
Arctan(Y/X), the complete phasor quantity can be derived and compared with
other current phasors calculated from other current pairs selected from the
same two rows of the Event Report. In
at the present sample the
phasor rms current value is:
Equation 9.1
IA
t
IA
1379
–2376
–1375
2380
event report column
X=present sample
Y =
previous
1/4 cycle
Magnitude =
X = 2380
Y
=
–13
75
Angle
= Arctan
= Arctan
Y
X
(
)
–
2380
(
)
=–30.0˚
Real Axis
A
xi
s
Ima
ginary
1/4 cyc.
(–1375)2 + (–2380)2 = 2749
IA
2749 A
30.0
–
=
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...