8.5
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Front-Panel Interface
Pushbuttons
history buffer, but a much smaller number of full event reports. The
EVENTS
command will display everything but the currents for the older, incomplete
history summaries. Use
{CANCEL}
or
{EXIT}
to return to the default display.
, at the end of this section, shows the EVENTS display structure.
STATUS
The
{STATUS}
pushbutton displays the relay status information in similar
fashion to the serial port
STA
command. When
{STATUS}
is pushed, the initial
display shows:
STATUS: [OK/WARN/FAIL]
FID=
SEL
-387-R103
(e.g., the first 12 characters of the FID string)
The STATUS line shows the worst state of the several parameters examined.
The right/left arrow keys can be used to view the rest of the FID string.
The up/down arrow keys are then used to manually scroll through the
diagnostic fields, showing the analog channel offsets, power supply voltages,
internal temperature, RAM (OK/FAIL), etc. The display remains in this scroll
sequence until either
{CANCEL}
or
{EXIT}
is pushed.
OTHER
The
{OTHER}
pushbutton is used to access several miscellaneous functions, and
mimics the corresponding serial port commands for these functions. Pushing
{OTHER}
provides a menu that prompts the user to select
DATE
,
TIME
,
TAR
get,
BKR
( breaker),
RESET51
, or
LCD
. These perform the same functions as the
serial port commands
DAT
,
TIM
,
TAR
,
BRE
, and
RES
. Use any arrow key
and
{SELECT}
to choose the function. These
{OTHER}
subfunctions are discussed
below in alphabetical order.
BKR
This function displays the breaker monitor accumulator values for internal and
external trips, the accumulated interrupted currents by pole, the percent
contact wear, and the time/date of last reset, for the selected breaker.
When BKR is selected, a second menu appears to prompt the user to select
Bk1
,
Bk2
,
Bk3
, or
Bk4
. Use the right/left arrow keys and
{SELECT}
to choose.
Another menu appears, asking whether
DISPLAY
or
RESET
is desired. Use the
right/left arrow keys and
{SELECT}
to choose.
If
DISPLAY
is selected, the display scrolls automatically, showing the Internal
and External trip counters for the breaker chosen, the phase currents
accumulated for each type of trip, and the percent contact wear by breaker
pole. The first two-line display shows
P1
, the second
P2
, and the third
P3
. The
fourth display shows
% wear
for each of the three poles, in integer values of
100 or less. The fifth display shows
Last Reset From
and the date/time of last
reset. Pushing
{SELECT}
will toggle between stop-scroll and resume-scroll, to
facilitate hand-recording of data values.
Push
{CANCEL}
to return to the
OTHER
main menu. Push
{EXIT}
to return to the
default display.
, at the end of this section, shows the full
OTHER/BKR
menu and
display structure.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...