E.11
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Compressed ASCII Commands
SEL-387-6 Relay
The command parameters, all optional, can be entered in any order. They are:
CEVENT Winding
Report (Default)
If
DIF
is not specified in the command line, the default report is the winding
currents report. To obtain a report, send the following:
CEV <Enter>
The relay responds:
<STX>
"FID","yyyy"<CR>
"FID=SEL-387-XXXX-V0-ZXXXXXX-DXXXXXXXX","yyyy"<CR>
"MONTH_","DAY_","YEAR_","HOUR_","MIN_","SEC_","MSEC_","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"FREQ","SAM/CYC_A","SAM/CYC_D","NUM_OF_CYC","EVENT","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,"xxxx","yyyy"<CR>
"IAW1","IBW1","ICW1","IAW2","IBW2","ICW2","IAW3","IBW3","ICW3","IAW4",
"IBW4","ICW4","VDC","TRIG","DIGITAL_ELEMENT_NAMES","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"z","RLY_BITS"<CR>
... (previous line repeated for SAM/CYC_A*NUM_OF_CYC)
"SETTINGS","yyyy"<CR>
"SETTINGS text","yyyy"<CR>
<ETX>
Report Types:
Description
DIF
Display differential information for the all elements.
R
Displays raw (unfiltered) analog data and raw station battery
Displays preceding 1.5 cycles (including reports with “L” options)
Allows S4, S8, S16, S32, and S64
Defaults to S16 samples/cycle
(default)
Display cosine filtered fundamental currents
on all windings and station battery averaged for 1 cycle
Report Options:
Description
n
Event number
Default to 1
S
x
Samples per cycle
x
= 4 or 8 (See “R” option)
Default to 4 if S
x
not specified
L
y
Display first y cycles of event report
y
= 1 – LER
Default to L15 if L
y
not specified
L
y
–
Displays event report from cycle
y
to end of report
L
y
–
w
Displays event report from cycle
y
to cycle
w
C
Default to 8 samples/cycle (same as
EVE C
)
NOTE:
If Sx and/or Ly are given, they
override all other parameters.
NOTE:
The L and U parameters are
supported for consistency with the
SEL-321 Relay. The C parameter is
used for SEL-2020 compatibility.
where:
xxxx
= are the data values corresponding to the first line labels.
yyyy
= the 4-byte ASCII representation of the hex checksum for
the line.
z
= “>” to mark where the event was triggered, “*” to mark
the maximum current for the event, with the “*”
overriding the “>”.
RLY_BITS
= relay element data, in hex ASCII, corresponding to the
DIGITAL_ELEMENT_NAMES
SETTINGS
= text refers to the current settings of the relay as described
in the event report section.
NOTE:
DIGITAL_ELEMENT_NAMES
consists of the text strings
representing the names for the Relay
Word bits from the element store
visible to the user, excluding the first
two front-panel rows.
NOTE:
If the analog current input
names (
IAW1
, etc.) have been changed
via the Analog Input Labels global
settings, they will appear in the above
report as set.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...