B.11
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
SEL-300 Series Relays Firmware Upgrade Instructions
Upgrade Procedure
select the directory on the hard drive where you want to
access the uncompressed files. Verify that these
uncompressed files have an .s19 extension.
Step 2. Type
REC <Enter>
at the SEL
boot !>
prompt to command
the relay to receive new firmware.
!>REC <Enter>
Caution! - This command erases the relays firmware.
If you erase the firmware, new firmware must be loaded into the relay
before it can be put back into service.
Step 3. The relay asks whether you want to erase the existing firmware.
Are you sure you wish to erase the existing firmware? (Y/N) Y <Enter>
Step 4. Type
Y
to erase the existing firmware and load new firmware.
(To abort, type
N
or press
<Enter>
).
The relay responds with the following:
Erasing
Erase successful
Press any key to begin transfer, then start transfer at the PC
<Enter>
Step 5. Press
<Enter>
to start the file transfer routine.
Step 6. Send new firmware to the relay.
a. From the
Transfer
menu in
HyperTerminal
, choose
Send File
b. In the
Filename
text box, type the location and
filename of the new firmware or use the
Browse
button
to select the firmware file.
c. In the
Protocol
text box, select
1K Xmodem
if this
protocol is available.
If the computer does not have
1K Xmodem
, select
Xmodem
.
d. Click
Send
to send the file containing the new
firmware.
You should see a dialog box similar to
.
Incrementing numbers in the
Packet
box and a bar
advancing from left to right in the
File
box indicate that
a transfer is in progress.
Receiving software takes 10–15 minutes at 38400 bps,
depending on the relay. If you see no indication of a transfer in
progress within a few minutes after clicking
Send
, use the
REC
command again and reattempt the transfer.
After the transfer completes, the relay displays the following:
Upload completed successfully. Attempting a restart.
A successful restart sequence can take as long as two minutes,
after which time the relay leaves SEL
BOOT
. You will see no
display on your PC to indicate a successful restart.
NOTE:
Unsuccessful uploads can
result from Xmodem time-out, a
power failure, loss of communication
between the relay and the computer,
or voluntary cancellation. Check
connections, reestablish
communication, and start again at
Step 2 on page B.11.
If you want to reload the previous
firmware, begin at Step 2 on page B.11
and use the firmware you saved in E.
Download Existing Firmware on
page B.9. Contact the factory for
assistance in achieving a successful
firmware upgrade.
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...