7.33
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
Entering
SHO P <Enter>
is an easy way to identify the port to which you are
presently connected.
Settings cannot be entered or modified with this command. Change settings
with the
SET P
command from Access Level 2. The following example shows
the factory default settings. Refer to
for
Settings
Sheets
.
=>>
SHO P <Enter>
Port 2
PROTO = SEL
SPEED = 19200 BITS = 8 PARITY = N STOP = 1
T_OUT = 0 AUTO = Y RTSCTS = N FASTOP = N
=>>
SHO R (Show SER Settings)
Access Levels 1, B, 2
SHOWSET R
displays the Sequential Events Recorder settings. The syntax
of the
SHO R
command follows:
SHO R Setting <Enter>
➤
Setting
specifies the setting name with which to begin. The
default is the first setting.
Settings cannot be entered or modified with this command. Change settings
with the
SET R
command from Access Level 2. Refer to
for information on all settings. Following is an example of the
display for the
SHO R
command.
=>>
SHO R <Enter>
SER1 =IN101, IN102, IN103, IN104, IN105, IN106
SER2 =OUT101, OUT102, OUT103, OUT104, OUT105, OUT106, OUT107
SER3 =0
SER4 =0
ALIAS1 =OUT101 B1TRIP
ALIAS2 =OUT105 B1CLOSE
ALIAS3 =OUT102 B2TRIP
ALIAS4 =OUT106 B2CLOSE
ALIAS5 =OUT103 B3TRIP
ALIAS6 =OUT107 B3CLOSE
ALIAS7 =NA
ALIAS8 =NA
ALIAS9 =NA
ALIAS10 =NA
ALIAS11 =NA
ALIAS12 =NA
ALIAS13 =NA
ALIAS14 =NA
ALIAS15 =NA
ALIAS16 =NA
ALIAS17 =NA
ALIAS18 =NA
ALIAS19 =NA
ALIAS20 =NA
=>>
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...