9.4
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Event Reports and SER
Standard 15-, 30-, or 60-Cycle Event Reports
XFMR 1 Date: 02/28/97 Time: 06:28:38.888
STATION A
Event: TRIP1 TRIP2 TRIP3 TRIP4 TRIP5
Targets: TRIP INST 87-1 87-2 87-3 50 51 A B C N W1 W2 W3 W4
Winding 1 Currents (A Sec), ABC: 123.4 123.4 123.4
Winding 2 Currents (A Sec), ABC: 123.4 123.4 123.4
Winding 3 Currents (A Sec), ABC: 123.4 123.4 123.4
Winding 4 Currents (A Sec), ABC: 123.4 123.4 123.4
Figure 9.1
Example Event Summary
The latest 80 event summaries are stored in nonvolatile memory and are
accessed by the
HISTORY
command. The
HIS C
command clears the event
summaries and corresponding full-length standard event reports from
nonvolatile memory. See
HIS (History of Events) on page 7.19
(Clear History and Events) on page 7.19
for more information.
Event Type
The
Event:
field shows the event type. The possible event types and their
descriptions are shown in
. Note the correspondence to the preceding
event report triggering conditions (see
Standard Event Report Triggering on
).
The order of precedence for listing the event type in the summary is:
TRIP
,
CLOSE
,
ER
,
PULSE
,
TRIG
). If more than one type of
report trigger occurs within the same report period, the type of highest
precedence will be shown in the
Event:
field of the report summary.
Targets
The target field shows all front-panel targets that were illuminated at the end
of the triggered event report. The targets include:
TRIP
,
INST
,
87-1
,
87-2
,
87-3
,
50
,
51
,
A
,
B
,
C
,
N
,
W1
,
W2
,
W3
, and
W4
.
NOTE:
SEL-387-0 firmware versions
R100–R105 display 99 event
summaries. SEL-387-6 firmware
versions R304 and R405 display 40
event summaries. All other firmware
versions display 80 event summaries.
Table 9.1
Event Types
Event
Event Triggered by:
TRIP1
Assertion of Relay Word bit TRIP1
TRIP2
Assertion of Relay Word bit TRIP2
TRIP3
Assertion of Relay Word bit TRIP3
TRIP4
Assertion of Relay Word bit TRIP4
TRIP5
Assertion of Relay Word bit TRIP5
CLS1
Assertion of Relay Word bit CLS1
CLS2
Assertion of Relay Word bit CLS2
CLS3
Assertion of Relay Word bit CLS3
CLS4
Assertion of Relay Word bit CLS4
ER
SEL
OGIC
control equations setting ER
PULSE
Execution of
PULSE
serial port command
TRIG
Execution of
TRIGGER
serial port command
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...