Date _______________
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
SET.5 of 35
SEL-387-0, -5, -6 Relay Settings Sheets
Group Settings (SET Command)
50N11 Torque Control (SEL
OGIC
control equation)
50N11TC
=
Residual Inst. O/C Level 2 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50N12P
=
50N12 Torque Control (SEL
OGIC
control equation)
50N12TC
=
Residual Inv.-Time O/C PU
(OFF, 0.5–16.0 A secondary) (5 A)
(OFF, 0.1–3.2 A secondary) (1 A)
51N1P
=
Residual Inv.-Time O/C Curve (U1–U5, C1–C5)
51N1C
=
Residual Inv.-Time O/C Time-Dial
(US 0.5–15.0, IEC 0.05–1.00)
51N1TD
=
Residual Inv.-Time O/C EM Reset (Y, N)
51N1RS
=
51N1 Torque Control (SEL
OGIC
control equation)
51N1TC
=
Winding 1 Demand Metering
Demand Ammeter Time Constant (OFF, 5–255 min)
DATC1
=
Phase Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
PDEM1P
=
Neg.-Seq. Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
QDEM1P
=
Residual Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
NDEM1P
=
Winding 2 O/C Elements
Winding 2 Phase O/C Elements
Phase Def.-Time O/C Level 1 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50P21P
=
Phase Level 1 O/C Delay (0–16000 cycles)
50P21D
=
50P21 Torque Control (SEL
OGIC
control equation)
50P21TC
=
Summary of Contents for SEL-387-0
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 200: ...This page intentionally left blank ...
Page 248: ...This page intentionally left blank ...
Page 380: ...This page intentionally left blank ...
Page 422: ...This page intentionally left blank ...
Page 440: ...This page intentionally left blank ...
Page 458: ...This page intentionally left blank ...
Page 516: ...This page intentionally left blank ...